Fluke 1738/EUS Three-Phase Power Quality Loggers

Fluke 1738/EUS Includes:

  • 1738 Power Logger
  • Power supply
  • Voltage test leads
  • Alligator clips (x4)
  • 12 in 1,500A flexible current probe (x4)
  • Soft case
  • Energy Analyze Plus software
  • Magnetic hanging strap
  • Magnetic voltage probes (x4)
  • WiFi/BLE adapter
  • Line cords
  • Color coding set
SKU:78436

MME Shopping Event

Hurry and get discounts on Most of MME Products up to 20%

Call for Price

10People watching this product now!

Fluke 1738 EUS Advanced Power Logger, EU and US version (includes current probes)

The Fluke 1738/EUS Advanced Power Logger is designed for comprehensive power quality analysis in both the European Union and the United States. It comes equipped with current probes to facilitate detailed monitoring and recording of power quality parameters. This tool is aimed at professionals who need to troubleshoot, analyze, and optimize electrical systems, ensuring compliance with power quality standards and enhancing system reliability and efficiency.

Fluke 1738EUS Features

  • Versatile, three-phase power loggers for conducting energy, load and power quality studies.
  • Automatically capture and log voltage, current, power, harmonics and associated power quality values, and capture dips, swells, and inrush currents with event waveform snapshots and high-resolution RMS profiles.
  • Convenient instrument powering directly from the measured circuit
  • Download and analyze every detail of energy consumption and power quality state of health with our automated reporting.

Fluke 1738/EUS Specifications:

Electrical Specifications of Fluke 1738B
Power Supply
Voltage range100 V to 500 V using safety plug input when powering from the measurement circuit
100 V to 240 V using standard power cord (IEC 60320 C7)
Power consumptionMaximum 50 VA (max. 15 VA when powered using IEC 60320 input)
Efficiency≥ 68.2% (in accordance with energy efficiency regulations)
Maximum no-load consumption< 0.3 W only when powered using IEC 60320 input
Mains power frequency50/60 Hz ±15%
BatteryLi-ion 3.7 V, 9.25 Wh, customer-replaceable
On-battery runtimeFour hours in standard operating mode, up to 5.5 hours in power saving mode
Charging time< 6 hours
Data Acquisition
Resolution16-bit synchronous sampling
Sampling frequency10.24 kHz at 50/60 Hz, synchronized to mains frequency
Input signal frequency50/60 Hz (42.5 to 69 Hz)
Circuit types1-φ, 1-φ IT, Split phase, 3-φ delta, 3-φ wye, 3-φ wye IT, 3-φ wye balanced, 3-φ Aron/Blondel (2-element delta), 3-φ delta open leg, Currents only (load studies)
Data storageInternal flash memory (not user replaceable)
Memory sizeTypical 10 logging sessions of 8 weeks with 1-minute intervals and 500 events¹
¹The number of possible logging sessions and logging period depends on user requirements.
Basic Interval
Measured parametersVoltage, current, aux, frequency, THD V, THD A, power, power factor, fundamental power, DPF, energy
Averaging intervalUser selectable: 1 sec, 5 sec, 10 sec, 30 sec, 1 min, 5 min, 10 min, 15 min, 30 min
Averaging time min/max valuesVoltage, Current: Full cycle RMS updated every half cycle (URMS1/2 according to IEC61000-4-30 Aux, Power: 200ms
Demand Interval (Energy Meter Mode)
Measured parametersEnergy (Wh, varh, VAh), PF, maximum demand, cost of energy
IntervalUser selectable: 5 min, 10 min, 15 min, 20 min, 30 min, off
Power Quality Measurements
Measured parameterVoltage, frequency, unbalance, voltage harmonics, THD V, current, harmonics, THD A, TDD
Averaging interval10 min
Individual harmonics2nd to 50th harmonic
Total harmonic distortionCalculated on 50 harmonics
EventsVoltage: dips, swells, interruptions, current: inrush current
Triggered recordingsFull cycle RMS updated every half cycle of voltage and current (Urms1/2 according to IEC61000-4-30)
Waveform of voltage and current (1738)
Standards Compliance
HarmonicsIEC 61000-4-7: Class 1
IEEE 519 (short time harmonics)
Power qualityIEC 61000-4-30 Class S, IEC62586-1 (PQI-S device)
PowerIEEE 1459
Power quality complianceEN50160 (for measured parameters)
Interfaces
USB-AFile transfer via USB flash drive, firmware updates
Max. current: 120 mA
WiFiFile transfer and remote control via direct connection or WiFi infrastructure
BluetoothRead auxiliary measurement data from Fluke Connect® 3000 series modules (requires 1738 or 1736 upgrade option)
USB-miniData download device to PC
Voltage Inputs
Number of inputs4 (3 phases and neutral)
Maximum input voltage1000 Vrms, CF 1.7
Input impedance10 MΩ
Bandwidth (-3 dB)42.5 Hz – 3.5 kHz
Scaling1:1 and variable
Measurement category1000 V CAT III/600 V CAT IV
Current Inputs
Number of inputs4, mode selected automatically for attached sensor
Input voltageClamp input: 500 mVrms/50 mVrms; CF 2.8
Rogowski coil input150 mVrms/15 mVrms at 50 Hz, 180 mVrms/18 mVrms at 60 Hz; CF 4; all at nominal probe range
Range1 A to 150 A/10 A to 1500 A with thin flexible current probe i17XX-flex1500 12″
3 A to 300 A/30 A to 3000 A with thin flexible current probe i17XX-flex3000 24″
6 A to 600 A/60 A to 6000 A with thin flexible current probe i17XX-flex6000 36″
40 mA to 4 A/0.4 A to 40 A with 40 A clamp i40s-EL
Bandwidth (-3 dB)42.5 Hz – 3.5 kHz
Scaling1:1 and variable
Auxiliary Inputs
Number of inputs2
Input range0 to ±10 V dc, 1reading/s
Scale factorFormat: mx + b (gain and offset) user configurable
Displayed unitsUser configurable (7 characters, for example, °C, psi, or m/s)
Wireless Connection
Number of inputs2
Supported modulesFluke Connect® 3000 series
Acquisition1 reading/s
Environmental Specifications
Operating temperature-10 °C to +50 °C (14 °F to 122 °F)
Storage temperature-20 °C to +60 °C (-4 °F to 140 °F), with battery: -20 °C to +50 °C (-4 °F to 122 °F)
Operating humidity10 °C to 30 °C (50 °F to 86 °F) max. 95% RH
30 °C to 40 °C (86 °F to 104 °F) max. 75% RH
40 °C to 50 °C (104 °F to 122 °F) max. 45% RH
Operating altitude2000 m (up to 4000 m derate to 1000 V CAT II/600 V CAT III/300 V CAT IV)
Storage altitude12,000m
EnclosureIP50 in accordance with EN60529
VibrationMIL-T-28800E, Type 3, Class III, Style B
SafetyIEC 61010-1
IEC Mains Input: Overvoltage Category II, Pollution Degree 2
Voltage Terminals: Overvoltage Category IV, Pollution Degree 2
IEC 61010-2-031: CAT IV 600 V / CAT III 1000 V
Electromagnetic compatibilityEN 61326-1: Industrial CISPR 11: Group 1, Class A
Korea (KCC): Class A Equipment (industrial broadcasting and communication equipment)
USA (FCC): 47 CFR 15 subpart B. This product is considered an exempt device per clause 15.103
Temperature coefficient0.1 x accuracy specification/°C
General Specifications
Color LCD display4.3-inch active matrix TFT, 480 pixels x 272 pixels, resistive touch panel
WarrantyInstrument and power supply: Two-years (battery not included)
Accessories: one-year
Calibration cycle: two-years
DimensionsInstrument: 19.8 cm x 16.7 cm x 5.5 cm (7.8 in x 6.6 in x 2.2 in)
Power supply: 13.0 cm x 13.0 cm x 4.5 cm (5.1 in x 5.1 in x 1.8 in)
Instrument with power supply attached: 19.8 cm x 16.7 cm x 9 cm (7.8 in x 6.6 in x 3.5 in)
WeightInstrument: 1.1 kg (2.5 lb)
Power supply: 400 g (0.9 lb)
Tamper protectionKensington lock slot
i17xx-flex 1500 12″ Flexible Current Probe Specifications
Measuring range1 to 150 A ac/10 to 1500 A ac
Nondestructive current100 kA (50/60 Hz)
Intrinsic error at reference condition*±0.7% of reading
Accuracy 173x + iFlex±(1% of reading + 0.02% of range)
Temperature coefficient over operating temperature range0.05% of reading/°C 0.09% of reading/°F
Working voltage1000 V CAT III, 600 V CAT IV
Probe cable length305 mm (12 in)
Probe cable diameter7.5 mm (0.3 in)
Minimum bending radius38 mm (1.5 in)
Output cable length2 m (6.6 ft)
Weight115 g
Probe cable materialTPR
Coupling materialPOM + ABS/PC
Output cableTPR/PVC
Operating temperature-20 °C to +70 °C (-4 °F to 158 °F) temperature of conductor under test shall not exceed 80 °C (176 °F)
Temperature, non-operating-40 °C to +80 °C (-40 °F to 176 °F)
Relative humidity, operating15% to 85% non-condensing
IP ratingIEC 60529:IP50
WarrantyOne-year
0 reviews
0
0
0
0
0

There are no reviews yet.

Be the first to review “Fluke 1738/EUS Three-Phase Power Quality Loggers”

Brand

Fluke

Fluke Corporation

Since its founding in 1948, Fluke has helped define and grow a unique technology market, providing testing and troubleshooting capabilities that have grown to mission critical status in manufacturing and service industries. Every new manufacturing plant, office, hospital, or facility built today represents another potential customer for Fluke products. From industrial electronic installation, maintenance and service, to precision measurement and quality control, Fluke tools help keep business and industry around the globe up and running. Typical customers and users include technicians, engineers, metrologists, medical-device manufacturers, and computer network professionals — people who stake their reputations on their tools, and use tools to help extend their personal power and abilities.

Datasheet

Mme-Pdfs-Image

Specifications